An undersized diesel generator can trip during equipment startup, while an oversized unit may increase purchasing and operating costs. Selecting the correct generator capacity is therefore one of the first decisions industrial buyers should make.
For factories, hospitals, construction sites and commercial buildings, the right generator size depends on actual electrical demand, starting current, load characteristics and operating conditions.
Most diesel generator manufacturers specify capacity in kVA, but electrical equipment commonly lists its power consumption in kW.
These two measurements are related but not identical.
kW represents active electrical power.
kVA represents apparent electrical power.
Power factor describes the relationship between them.
The basic formula is:
For a generator with a power factor of 0.8:
Generator Rating | Power Factor | Active Power |
|---|---|---|
50 kVA | 0.8 | 40 kW |
100 kVA | 0.8 | 80 kW |
200 kVA | 0.8 | 160 kW |
500 kVA | 0.8 | 400 kW |
800 kVA | 0.8 | 640 kW |
These are illustrative calculations, not individual product specifications. Always check the manufacturer's rated power factor and technical datasheet.
Before requesting a quotation from a generator factory, prepare a list of all equipment that will operate from the generator.
For example, a small manufacturing facility might have the following connected loads:
Equipment | Quantity | Power per Unit | Total Load |
|---|---|---|---|
Production motors | 3 | 15 kW | 45 kW |
Air compressors | 1 | 22 kW | 22 kW |
Lighting | 1 system | 5 kW | 5 kW |
Office equipment | 1 system | 3 kW | 3 kW |
Water pumps | 2 | 5 kW | 10 kW |
Total | 85 kW |
At a power factor of 0.8, the theoretical apparent power requirement is:
However, this does not automatically mean that a 110 kVA generator is suitable.
Motor starting currents, simultaneous operation, load fluctuations and future expansion must also be considered. A qualified electrical engineer should verify the final selection.
One common mistake among overseas buyers is comparing generator models using only their maximum standby rating.
Prime Power (PRP) and Emergency Standby Power (ESP) describe different operating conditions.
Feature | Prime Power (PRP) | Standby Power (ESP) |
|---|---|---|
Main purpose | Variable-load operation | Emergency backup |
Operating pattern | Regular or continuous duty within rating limits | Limited emergency operation |
Load profile | Variable | Emergency demand |
Overload capability | Subject to applicable rating standards | Generally not available |
Typical applications | Construction, industrial operations | Backup for commercial buildings |
If a factory needs electricity every day because grid power is unavailable, the prime power rating is generally the more relevant figure.
For emergency backup, standby power may be appropriate, provided the generator is sized according to the applicable rating standard.
BAIFA's BF-V206 provides a useful example of how buyers can evaluate a generator using actual technical information.
According to its published technical sheet, the model features:
Engine: VOLVO TAD732GE.
Rated voltage: 400V.
Frequency: 50Hz.
Engine speed: 1500 rpm.
Displacement: 7.15 liters.
Six-cylinder inline configuration.
Turbocharged air intake with air-to-air intercooling.
The engine technical sheet also lists a maximum standby engine power of 179 kW at rated speed. This is an engine specification, not the generator's electrical kW rating. The complete generator's PRP and ESP ratings should be checked separately in the relevant product datasheet.
This distinction matters because an engine's mechanical output should never be confused with the generator set's rated electrical output.
Generator frequency is particularly important for international procurement.
Different markets and applications may require different electrical configurations.
Market | Common Frequency | Typical Voltage Examples |
|---|---|---|
China | 50Hz | 380V/400V |
India | 50Hz | 415V |
UK | 50Hz | 400V |
USA | 60Hz | 480V |
Turkey | 50Hz | 400V |
Italy | 50Hz | 400V |
These are common three-phase industrial supply examples, not universal specifications. Actual project requirements must be confirmed before ordering.
A generator designed for 50Hz operation should not simply be connected to a 60Hz system without checking engine speed, alternator characteristics and electrical configuration.
BAIFA provides both 50Hz and 60Hz generator configurations across its product portfolio.
Besides the calculated load, several operating conditions can influence generator performance.
Altitude: Higher elevations reduce air density, potentially affecting engine output.
Ambient temperature: High temperatures can increase cooling demands and reduce available engine power.
Motor starting: Compressors, pumps and large motors may require significantly more power during startup.
Load expansion: Industrial facilities may add machinery after installation. Allowing reasonable expansion capacity can prevent premature replacement.
Harmonic loads: UPS systems, variable-frequency drives and other electronic equipment may require additional alternator and system considerations.
A reliable generator manufacturer should review the load list rather than simply recommend a model based on a single kVA figure.
BAIFA provides different generator engine series and power configurations, including VOLVO, Cummins, Perkins, MTU and other engine options.
Its manufacturing facilities in Wuxi support generator assembly and customized equipment configurations.
For an accurate quotation, buyers should provide:
Total connected load.
Motor starting information.
Required voltage and frequency.
Prime or standby operating requirements.
Ambient temperature and installation altitude.
Enclosure and fuel tank requirements.